- Insulation test range: 0.01 MOhms to 10 GOhms
- Insulation test voltages:50 V, 100 V, 250 V, 500 V, 1000 V
- Save both time and money with Automatic calculation of Polarization Index and Dielectric Absorption Ratio (only available on the1507)
- Make repetitive tests simple and easy with the 1507s Compare (Pass/Fail) function (only available on the 1507)
- Repetitive or hard-to-reach testing is easy with the remote test probe
- Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection
- Auto-discharge of capacitive voltage for added user protection
- AC/DC voltage: 0.1 V to 600 V
- 200 mA Continuity
- Resistance: 0.01 Ohms to 20.00 kOhms
- Save battery power with auto power off
- Read measurements easily with large, backlit display
- CAT IV 600 V overvoltage category rating for added user protection
- Remote probe, test leads, probes and alligator clips included with each tester
- Accepts optional Fluke TPAK magnetic hanging system to free your hands for other work
- Four AA alkaline batteries (NEDA 15 A or IEC LR6) for at least 1000 insulation tests
- One year warranty
- Range: 600.0 V
- Resolution: 0.1 V
- 50 Hz to 400 Hz +/- (% of Rdg + Digits): +/- (2 % + 3)
- Input impedance: 3 MOhms (nominal), < 100 pF
- Common mode rejection ratio (1 kOhms unbalanced): > 60 dB at dc, 50 or 60 Hz
- Overload Protection 600 V rms or dc
- 20.00: Ohms 0.01 Ohms
- 200.0: Ohms 0.1 Ohms
- 2000: Ohms 1.0 Ohms
- 20.00: kOhms 0.01 kOhms
- Accuracy: +/- (1.5 % + 3)
- Overload Protection: 2 V rms or dc
- Open Circuit Test Voltage: > 4.0 V, < 8 V
- Short circuit current: > 200.0 mA
- Measurement Range 1507: 0.01 MOhms to 10 GOhms
- Test voltage: 50 V, 100 V, 250 V, 500 V, 1000 V
- Test Voltage: Accuracy + 20 %, – 0 %
- Short circuit current: 1 mA nominal
- Auto Discharge: Discharge time < 0.5 second for C = 1 pF or less
- Live circuit indicator: Inhibit test if terminal voltage > 30 V prior to initialization of test
- Maximum Capacitive Load: Operable with up to 1 pF load
- 50 V: +/-(3 % + 5)
- 100 V: +/-(3 % + 5)
- 250 V: +/-(1.5 % + 5)
- 500 V: +/-(1.5 % + 5)
- 1000 V: +/-(1.5 % + 5) to 2000 MOhms, ±(10 % + 3) above 2000 MOhms
- Maximum voltage applied to any terminal: 600 V ac rms or dc
- Storage Temperature-40 C to 60 C (-40 F to 140 F)
- Operating Temperature-20 C to 55 C (-4 °F to 131 F)
- Temperature Coefficient0.05 x (specified accuracy) per C for temperatures 28 °C ( 82 F)
- 0 % to 95 % @ 10 C to 30 C (50 F to 86 F)
- 0 % to 75 % @ 30 C to 40 C (86 F to 104 F)
- 0 % to 40 % @ 40 C to 55 C (104 F to 131 F)
- Vibration Random, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument
- Shock 1 meter drop per IEC 61010-1 2nd Edition (1 meter drop test, six sides, oak floor)
- Electromagnetic compatibility: In an RF field of 3 V/M, accuracy = specified accuracy (EN 61326-1:1997)
- Safety Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement category IV 600 V (CAT IV)
- Certifications: CSA per standard CSA/CAN C22.2 No. 61010.1-04; TUV per standard IEC/EN 61010-1 2nd Edition
- BatteriesFour AA batteries (NEDA 15A or IEC LR6)
- Battery Life Insulation test use: Tester can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MOhms with a duty cycle of 5 seconds on and 25 seconds off.
- Resistance measurements: Tester can perform at least 2500 earth bond resistance measurements with fresh alkaline batteries at room temperature. These are standard tests of 1 Ohms with a duty cycle of 5 seconds on and 25 seconds off.
- Size 5.0 cm H x 10.0 cm W x 20.3 cm L (1.97 in H x 3.94 in W x 8.00 in L)
- Weight550 g (1.2 lb)
- IP Rating IP40
- Altitude: Operating: 2000 m CAT IV 600 V, 3000 m CAT III 600 V
- Non-operating (storage): 12,000 m
- Over-range capability: 110 % of range
- Included accessories: TL224 Test Leads, TP74 Test Probes, clips PN 1958654 (red) and PN 1958646 (black), holster and remote probe
- Remote probe
- Test leads
- Test probes
- Alligator clips
- Holster
- User documentation
Specifications:
AC/DC Voltage Measurement
Accuracy:
Earth bond resistance measurement
Range/Resolution
Insulation specifications
Measure Accuracy:
General Specifications
Relative Humidity
Insulation Tester Includes: